Astar HT-3300 Dokumentacja Strona 138

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 137
128
Reference Manual
00809-0100-4811, Rev DA
Appendix A: Reference Data
January 2015
Reference Data
Figure A-13. Lower Transition Zone
For a flexible single lead probe with chuck, the lower transition zone is measured upwards from
the upper part of the clamp.
Measuring range and minimum dielectric constant
16 in. (0.4 m) to 77 ft. (23.5 m)
See Table A-4 for each probe’s measuring range and minimum dielectric constant. Due to the
measuring range depending on the application and factors described below, the values are
guidelines for clean liquids. For more information, ask your local Emerson Process Management
representative.
Table A-4. Measuring Range and Minimum Dielectric Constant
Rigid single lead /
segmented rigid
single lead
Flexible single
lead
Coaxial Rigid
twin lead
Flexible
twin lead
Maximum
measuring
range
9 ft 10 in. (3 m)
for 8 mm probes (code 4A)
19 ft 8 in. (6 m)
for 13 mm probes (code 4B, 4S)
77 ft 1 in.
(23.5 m)
19 ft 8 in.
(6 m)
9 ft 10 in.
(3 m)
77 ft 1 in.
(23.5 m)
Minimum
dielectric
constant
2.5 (or 1.7 if installed in a
metallic bypass or
stilling well)
(1)
(1) May be lower depending on installation.
2.5 up to 36 ft
(11 m)
(2)
5.0 up to 66 ft
(20 m)
7.5 up to 77 ft 1 in.
(23.5 m)
(2) In pipes with a diameter less than 8 in. (20 cm), the minimum dielectric constant is 2.0.
1.5 1.9
1.6 up to 33 ft
(10 m)
2.0 up to 66 ft
(20 m)
2.4 up to 77 ft 1 in.
(23.5 m)
Przeglądanie stron 137
1 2 ... 133 134 135 136 137 138 139 140 141 142 143 ... 223 224

Komentarze do niniejszej Instrukcji

Brak uwag